AC C-TEC 2420-8

Capacitor buffered Power Supply

Type       :   AC C-TEC 2420-8
Art. No:  :   NCPA0746G01003

  

 

 

 

 

Short description

 

The DC-UPS of the series AC C-TEC includes ultra-capacitors as energy storage inside the housing. During normal operation the power supply supplies the connected loads and charges at the same time the capacitors. In case of an interruption of the mains supply, the energy of the ultra-capacitors is released regulated. The load is supplied by the back-up module until the ultra-capacitors are discharged. The back-up time depends on the state of charge of the capacitors and on the discharge current.

 

 

The DC-UPS has the following characteristics:

·         Maintenance-free because of long-life ultra-capacitors

·         Microcontroller based charging and discharging of the ultra-capacitors

·         Control of operation and status of charge with potential-free contacts and LED

·         Low wiring effort necessary because of the integration of mains adaptor and energy store

·         compatible to TECControl shutdown-software

·         Communication with an IPC via USB or RS232 cable possible

·         adjustable with USB interface

·         Capacity extension possible with external capacitor extension modules

·         Cyclic capacitor test during mains operation

·         Big temperature range -40 C up to 60 C

Technical Data

Input

 

Nominal input voltage

400 / 500 V AC

Nominal frequency

45 – 66 Hz

Nominal input voltage range

340 V – 550 V AC

Rated input current

0,95 A AC (Ue = 400 V AC)

Max. pre-fusing

3 x 2 A (T)

Max input current

32 A / 0,5 ms

Output

 

Nominal output voltage (in mains operation)

24,0 V DC ± 0,5 V

Nominal output voltage (in back-up operation)

24,0 V DC

Max. nominal output current (in mains operation)

17,5 A DC @ 60 °C
20,0 A DC @ 50 °C

Max. nominal output current (in back-up operation)

17,5 A DC @ 60 °C
20,0 A DC @ 50 °C

Max. power loss 'worst-case'

65 W (Ua = 24,0 V DC)

Energy

8 kJ

Back-up time

344 s @ 1 A / 12 s @ 20 A

General information

 

Max. load message contact:

Mains operation, Uc >, error

30 V DC max. 0,5 A

Max. load message contact Shutdown

24 V DC (6 – 40 V DC)

Earth leakage current

< 3,5 mA

Parallel operation

no

Serial operation

no

Protective system

IP20

Operational temperature

-40 … 60 °C

Storage temperature

-40 … 70 °C

Relative humidity

< 95 % condensation not permissible

Max. mounting heigth (without load reduction)

2000 above sea level

Dimensions (H x W x D)

192,5 mm, 170 mm, 198 mm

Weight

3,5 kg

Fixation

Mounting bracket for mounting plate

Downloads

Description
Version
File Format

Datasheet

161013PDF
Quickstart-PDF
Manual161013PDF
3D Model-SAT
EPLAN Macro140703edz

To download the manual, the 3D model and the EPLAN Macro please log in here