| Short description
The buffered DC power supply of the AC C-TEC series includes ultra-capacitors as energy storage inside the housing. During normal operation this capacitor is charged from AC-mains. The connected DC consumers are supplied as well from AC mains. In case of an interruption of the AC supply, the energy of the ultra-capacitor is realesed regulated. With a dc/dc converter the load is supplied from the capacitor until it is discharged. The backup time depends on the state of charge of the capacitor and the discharge current. The power supply has the following characteristics:
|
---|
Nominal input voltage | 115 V…230 V AC ±15 % | |
Nominal input voltage range | 97,8 V…264,5 V AC ±0 % | |
Nominal frequency | 47 Hz…63 Hz | |
Nominal input current | 1,5 A @ 115 V AC 0,75 A @ 230 V AC | |
Max. inrush current | 30 A / 2 ms | |
Output | ||
Nominal output current | 3 A -13 % +9 % | |
Nominal output voltage (in mains operation) | 24,3 V DC ±2 % | |
Output voltage (in back-up operation) | 23,5 V DC ±2 % | |
Energy (typical) |
| 1,5 kJ @ (Ua = 22,8 V DC, Ia = 0,6 A) |
Current limitation | See chapter 5.5 Short-circuit | |
Max power loss ‚worst-case‘ | 12 W | |
efficiency | 88% @ (Ue=230 V AC; Ua=24,3 V DC; Ia=INenn) | |
Fuse | ||
Internal device protection | 2,5 A (T), 250 V | |
Fusing DC-output circuit (external) | 3,15 A (T) | |
General | ||
Protective System | IP20 | |
Operational temperature | -40 °C…60 °C | |
Storage temperature | -40 °C…60 °C | |
Rel. humidity | ≤95% no condensation | |
Max. installation height (without load reduction) | 2000 m above sea level | |
Dimensions (H x W x D) | 157 mm x 72 mm x 139 mm | |
Weight | 0,85 kg |