AKKUTEC 2440

Battery buffered DC-UPS

Type      :   AKKUTEC 2440
Art.-No. :   NBPA P33G1M01

 

  

Short Description

The battery backed up DC power supply in the AKKUTEC range uses the standby-parallel principle of operation and, in conjunction with a lead accumulator, ensures that the DC power supply is reliably maintained in the case of a mains power failure.

 

  •  The power supply has the following features:

  • Switched primary, switched power supply with I/V charging characteristic

  • Microcontroller-based battery management

  • Temperature compensation for charging voltage by means of external sensor module (optional module)

  • Display and control panel for switch cupboard door installation or surface mounting (option)

  • TEC-Bus on RS 232-Interface (optional module)

Technical Data 

Input

Input voltage

400…500 V AC -15 % / +10 % (340…550 V AC)

Frequency

47…63 Hz

Input current

2,75 A @ 400 V AC / 2,2 A @ 500 V AC

Inrush current

≤ 65 A/5 ms

Nominal input power

1151 W
@ (Ue = 400 V AC, Ua = 26,4 V DC, Ia = 40 A)

Output

Nominal output voltage

24 V DC

Output voltage (without temperature tracking)

19,8…26,8 V DC ±0,4 %

Output voltage (with temperature tracking)

19,8…28,0 V DC ±0,4 %

Output voltage (boost charging)

28,6 V DC

Final charging voltage (without/with temperature tracking)

26,8 V DC ±0,4 % / 26,5…28,0 V DC ±0,4 %

Load shedding

19,8 V DC ±0,4 %

Nominal output current

40 A

Constant current limitation

1,05…1,1*INom

Self-consumption current (in back-up operation)

135 mA

Max. power loss ‚worst-case‘

115 W

Efficiency

91,5 %
@ (Ue = 400 V AC, Ua = 26,4 V DC, Ia = 40 A)

Charging characteristics

IU-characteristics DIN 41773-1

Fusing

Fusing battery circuit (external)

40 A (T), 250 V

Fusing output (external)

40 A (T), 250 V

Pre-fusing

4 A (T), 250 V

In General

Protective systeme housing

IP20

Overvoltage category

II

Degree of pollution

2

Battery type

Lead accumulator*

dimensions (H x WB x D) standard unit

180 mm x 290 mm x 150 mm

weight standard unit (witout batteries)

 

Operational temperature
operational temperature UL tested

0 °C … +40 °C
+10 °C … +40 °C

Storage temperature

0 °C … +50 °C

Relative humidity

≤95 % non-condensing

Max. height above sea level (without load reduction)

2000 m

Downloads

Description
Version
File Format

Datasheet

210602PDF
Quickstart AKKUTEC 2440-0  + NBBH 2407-PDF
Manual210604PDF
Manual AKKUTEC 2440 IPC170704PDF
EPLAN Macro140703edz
3D-Modell151009stp