AKKUTEC 2405

Battery buffered DC-UPS

Typ       : AKKUTEC 2405
Art.-No. : NBPA0616G01101

 

Short Description

The battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.
The back-up time is depending from the state of charge of the accumulator and of the discharge current.

The power supply has the following features:

  • Battery charger with I/U-charging characteristics
  • Battery management by micro-controller
  • Battery voltage tracking of the charging voltage by external sensor module (optional)
  • USB interface: with corresponding drivers and Schneider TECControl Software the message contacts can be controlled and a Shut-Down/Restart can be made.

Technical Data

Nominal input voltage115 ... 230 V AC ±15% 
Nominal frequency47 ... 63 Hz
nominal input current

1,4 A - 115 V AC

0,7 A - 230 V AC

output voltage without battery26,8 V DC ±0,4%
output voltage with battery19,8 V DC - 26,8 V DC
nominal output current5 A DC
Charge end voltage with temp.-sensor @ 25°27,0 V DC at 25°C

Charge end voltage without temp.-sensor

26,8 V DC ± 0,4%
Efficiency88,0 %
Battery type

Pb-Akku, maintenance-free

Pb- Akku maintenance-free (Option with changed characteristic)

Buffer timeDepending on battery and load
Degree of protectionIP 20

Operating temperature

recommended for battery

0 ... 45 °C

0... 25°C

Storage temperature0... 50°C
Max. altitude (without derating)1000 m above sea level
Dimensions (H x W x D)160 mm x 75 mm x 150 mm
Weight approximately 1,0 kg
Fixation

Snap-on mounting for DIN top hat rail

or mounting bracket for mounting plate

Norms and RegulationsEN 50178 / EN60950
UL approvals

UL 508

C22.2

For more details see datasheet.

Downloads

Description
Version
File Format

Datasheet

180125PDF
Quickstart AKKUTEC 2405-0 + NBBH 2401-PDF
Manual180125PDF
EPLAN Macro140703edz

To download the manual and the EPLAN Macro please log in here