AKKUTEC 2405

Battery buffered DC-UPS

Typ       : AKKUTEC 2405
Art.-No. : NBPA0616G01101

 

Short Description

The battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.
The back-up time is depending from the state of charge of the accumulator and of the discharge current.

The power supply has the following features:

  • Battery charger with I/U-charging characteristics
  • Battery management by micro-controller
  • Battery voltage tracking of the charging voltage by external sensor module (optional)
  • USB interface: with corresponding drivers and Schneider TECControl Software the message contacts can be controlled and a Shut-Down/Restart can be made.

Technical Data

Nominal input voltage115 ... 230 V AC -15% +10%
Nominal frequency47 ... 63, Hz
Max. nominal input current
Max charging current0,5 A
Nominal output voltage24 V DC
Output voltage range (with temp.-sensor)
19,8 V DC ... 27,8 V DC
Output voltage range (without temp.-sensor)
19,8 V DC ... 26,8 V DC
Max. nominal output current5 A DC
Charge end voltage with temp.-sensor @ 25°27,1 V DC ± 0,4%

Charge end voltage without temp.-sensor

26,8 V DC ± 0,4%
Efficiency88,0 %
Battery type

Pb-Akku, maintenance-free

Pb- Akku maintenance-free (Option with changed characteristic)

Buffer timeDepending on battery and load
Degree of protectionIP 20
Operating temperature0 ... 40 °C
Storage temperature
Relative humidity
Max. altitude (without derating)
Dimensions (H x W x D)160 mm x 75 mm x 150 mm
Weight approximately 1,6kg
Norms and RegulationsEN 50178 / EN60950
UL approvals

UL 508

C22.2

For more details see datasheet.

Downloads

Description
Version
File Format

Datasheet

130809PDF
Quickstart AKKUTEC 2405-0 + NBBH 2401-PDF
Manual160727PDF
EPLAN Macro140703edz

To download the manual and the EPLAN Macro please log in here