proTECTO 19" 1000 - 3000 VA

 

Short description

On-line UPS-system according to DIN EN 62040-3 (VFI-SS-111) with sinus soidal output voltage in each operation mode, RS232 interface and Shutdown Software for Windows NT/2000/XP/2003/Vista, Novell and Linux system software. The back-up time of the system can be increased by connecting additional external battery modules.

Technical Data

model proTECTO 19´

1000

1500

2200

2200 ER

3000

3000 ER

rating

 

rating in VA

1000

1500

2200

2200

3000

3000

rating in W

900

1350

1980

1760

2700

2400

back-up time

back-up time in minutes

100% load

7

6

6

0

5

0

   50% load

12

10

10

0

9

0

input

 

nominal voltage

220 / 230 / 240 V AC

input voltage range at 50% load

140 – 276 V

input voltage range at 100% load

184 – 276V

input frequency range

45 up to 65 Hz

nominal frequency

standard 50 Hz, configurable on 50 Hz, 60 Hz or auto select

tolerance of frequency

± 5 Hz

output
output voltage230 V (adjustable to 220 or 240 V)

tolerance of output voltage - dynamic
(load impact 0 to 100%)

≤ 5 %
bypass
voltage tolerance for switch over180 – 264 V
tolerance of frequencyfrom ± 0,5 Hz til ± 5Hz adjutable

Downloads

Description
Version
File Format

Datasheet

04-2011PDF