MPM 10 - 100 kVA

 

 

Short description

On-Line UPS-system in double conversion technology according to IEC / EN 62040-3 (VFI-SS-111) with three-phase input and single phase output, output transformer and sinus soidal output voltage in each operation mode, graphic display, LED display, RS232 interface, potentialfree alarms, shutdown-software for Windows NT/2000/XP/2003/ Vista, Novell and Linux system software. Optionally up to 8 systems may be switched in parallel. The back-up time of the systems can be increased by the connection of additional battery extension moduls.

Technical Data

model                MPM

10

15

20

30

40

60

80

100

 

rating

 

rating in kVA

10

15

20

30

40

60

80

100

rating in kW

9

13,5

18

27

36

54

72

90

 

back-up time in minutes with standard batteries

 

at 100 % load

6

7

13

on request

at 50% load

15

20

35

on request

 

input rectifier

 

nominal voltage

400 V

input voltage range

400 ±20%  (320 – 480 V)

nominal frequency

50 or 60 Hz automatic recognition

tolerance of frequency

± 5Hz

nominal input current      [A]

16

24

31

46

62

93

124

152

maximum input current   [A]

22

34

45

67

89

134

178

220

inrush current

< In (Softstart)

power factor  (cos j)

> 0,90

power factor  (cos j)

CLEAN Version

> 0,90

harmonic distortion THDI

< 25%

harmonic distortion THDI

CLEAN Version

< 5%

„Hold-Up Zeit“

20 ms

 

 

Downloads

Description
Version
File Format

-

--