MP 100 - 500 kVA HIP

 

Short description

On-Line UPS-system in double conversion technology according to IEC / EN 62040-3 (VFI-SS-111) with three-phase in- and output, iGBT rectifier, output transformer for galvanical separation and sinus soidal output voltage in each operation mode, LCD and LED display, RS232 interface, 2 slots for SNMP boards,alarm interface and shutdown-software for Windows NT/2000/XP/2003/ Vista, Windows 7, Novell and Linux system software. Optionally up to 8 systems may be switched in parallel. The back-up time of the systems is designed according to customer requirement with the connection of battery modules.

Technical Data 

model

MP 300 HIP

MP 400 HIP

MP 500 HIP

 

rating

 

rating in kVA

300

400

500

rating in kW

270

360

450

 

back-up time in minutes with standard batteries

 

at 100 % load

on request

at 50% load

on request

 

input rectifier

 

nominal voltage

400 V

input voltage range

400 V ±20%  (320 – 480 V) at 85% load

nominal frequency

50 or 60 Hz automatic recognition

tolerance of frequency

45 – 65 Hz

nominal input current           [A]

423

564

702

maximum input current [A]

476

635

794

inrush current

< In (Softstart)

Softstart 0 – 100%

0 – 120 s

power factor (cos j)

≥ 0,99

harmonical distortion THDI

≤ 3%

 

 