MP10-80 kVA

 

Short description

On-Line UPS-system in double conversion technology according to IEC / EN 62040-3 (VFI-SS-111) with three-phase in- and output, output transformer and sinus soidal output voltage in each operation mode, graphic display, LED display, RS232 interface, potentialfree alarms, shutdown-software for Windows NT/2000/XP/2003/ Vista, Novell and Linux system software. Optionally up to 8 systems may be switched in parallel. The back-up time of the systems can be increased by the connection of additional battery extension moduls.

 

Technical Data 

model                            MP

10

15

20

30

40

60

80

60 12-puls

80 12-puls

 

rating

 

rating in kVA

10

15

20

30

40

60

80

60

80

rating in kW

9

13,5

18

27

36

54

72

54

72

 

back-up time in minutes with standard batteries

 

at 100 % load

6

7

13

on request

at    50% load

15

20

35

on request

 

input rectifier

 

nominal voltage

400 V

input voltage range

400 ±20%  (320 – 480 V)

nominal frequency

50 or 60 Hz automatic recognition

tolerance of frequency

± 5Hz

nominal input current     [A]

16

24

31

46

62

93

124

93

124

maximum input current [A]

22

34

45

65

87

131

175

131

175

inrush current

< In (Softstart)

power factor  (cos j)

> 0,9

power factor  (cos j)

CLEAN Version

> 0,93

> 0,95

harmonical distortion THDI

< 25%

< 5%

harmonical distortion THDI

CLEAN Version

< 5%

< 3%

„Hold-Up Zeit“

20 ms

 

 

Downloads

Description
Version
File Format

-

--